Comparative of Two Building Envelopes for Energy Efficiency and Environmental Sustainability
1
Architecture Department,
Bharati Vidyapeeth College of Architecture,
Mumbai University, Navi Mumbai,
Maharashtra
India
Corresponding author Email: shraddhakapadia.26@gmail.com
Copy the following to cite this article:
Kapadia S. Comparative of Two Building Envelopes for Energy Efficiency and Environmental Sustainability. Curr World Environ 2025;20(1).
Copy the following to cite this URL:
Kapadia S. Comparative of Two Building Envelopes for Energy Efficiency and Environmental Sustainability. Curr World Environ 2025;20(1).
Citation Manager Publish History
Select type of program for download
Endnote EndNote format (Mac & Win) | |
Reference Manager Ris format (Win only) | |
Procite Ris format (Win only) | |
Medlars Format | |
RefWorks Format RefWorks format (Mac & Win) | |
BibTex Format BibTex format (Mac & Win) |
Article Publishing History
Received: | 2025-02-20 |
---|---|
Accepted: | 2025-04-21 |
Reviewed by: | ![]() ![]() |
Second Review by: |
![]() ![]() |
Final Approval by: | Lam Sze Mun |
Introduction
Recently, managing energy resources has surfaced as a key global priority, driven by environmental impact of Carbon dioxide emissions as well as other greenhouse gases. These emissions are largely responsible for the acceleration of climate change, leading to rising global temperatures, unpredictable weather patterns, and adverse effects on biodiversity. Simultaneously, the rapid depletion of fossil fuels, which have long been the main source of energy, further exacerbates the problem.1 As globalization progresses, the need for energy has increased dramatically, exerting considerable strain on both natural resources and the environment. Among the many sectors contributing to energy consumption, the hospitality industry has emerged as a key player. With the growth of tourism worldwide, resorts have become prominent contributors to the escalating energy crisis. 2
The hospitality sector, with its diverse and large-scale facilities, demands a significant amount of energy to operate effectively. Hotels and resorts, in particular, are energy-intensive due to their complex and content-specific design, which includes numerous functional areas like guest rooms, dining facilities, conference halls, kitchens, and recreational zones. Each of these spaces has distinct energy requirements, resulting in elevated total energy usage.3 The collective energy needs for heating, cooling, illumination (lighting), ventilation, and running different appliances lead to significant carbon emissions, which further intensify the environmental harm caused by the tourism sector. This presents a significant challenge for Hospitality industry stakeholders and policymakers, who must balance the need for energy consumption with the urgency of minimizing environmental impact.
One key area through which energy consumption can be optimized is the envelope of the building, which is crucial for the thermal efficiency of a resort.4 The building envelope—comprising walls, roofs, windows, and floors—acts as a barrier between the interior environment and the external climate. Its thermal properties directly affect energy used to stabilize indoor conditions of the structure, along with general comfort level of visitors. A thoughtfully crafted envelope can greatly diminish the reliance on artificial heating and cooling, resulting in decreased energy use and a smaller carbon footprint. And, poor thermal performance can result in excessive energy use, thereby increasing environmental impact.5
Considering these issues, this study’s objective is to investigate the efficiency of the exterior shell (envelope) of the resort building located in Matheran, a renowned hill station in India. The focus will be on assessing the envelope’s role in the resort’s energy conservation, considering its thermal properties, design features, and material choices. Through the examination of these elements, the research seeks to uncover possibilities for enhancing energy efficiency, diminishing energy usage, and lessening the project’s environmental footprint. Furthermore, the paper will assess the possibilities of incorporating sustainable construction methods and energy-saving technologies, including passive design approaches, renewable energy systems, and high-performance insulation materials, to improve the thermal efficiency of buildings. 6
Given the growing concern over environmental degradation and the urgent need for energy conservation in the hospitality sector, this research hopes to contribute valuable insights that can guide future resort designs, renovations, and operational practices towards greater sustainability and energy efficiency. Through a deeper understanding of the thermal performance of envelopes, the hospitality industry can take meaningful steps towards reducing its carbon footprint while ensuring the comfort and satisfaction of guests.
Need of the Research
Over the past several years, there is notable rise in tourism in Matheran, considering its location from both Mumbai and Pune. The town, known for its serene landscapes, lush green surroundings, and the tranquility, attracts thousands of tourists, has witnessed a consistent rise in visitors. This influx of tourists has directly impacted local businesses, resorts, and home stays, which have become a primary source of livelihood for many residents. Despite Matheran being designated as an Eco-sensitive zone (ESZ) in 2003, there has been a rise in the construction of new
buildings and transformation of residences as family-run lodging. This growth continues despite the regional authority’s imposition of a ban on any new construction in the region. The primary objective behind the ban was to protect the fragile ecosystem of Matheran. However, this increase in tourism and hospitality developments has created a paradox, where the rise in facilities contradicts the environmental preservation efforts aimed at maintaining Matheran’s natural beauty. 7
A serious spurt in tourists puts tremendous stress on Matheran’s infrastructure, including its transportation, waste management, water supply, and most notably, energy needs. This unregulated growth of both new and existing resorts, in tandem with the influx of tourists, has led to escalating energy demands. These demands are satisfied by traditional energy sources like electricity, fuel, wood, and oils, which lead to a higher carbon footprint. This pressure on Matheran’s energy resources, combined with the area’s fragile ecosystem, can severely disrupt its environmental balance, further compromising its allure and beauty.
The essence of tourism in Matheran lies in its environment. Tourists come for the peace, quiet, and natural surroundings, making it imperative to conserve the town’s ecological quality. The continued growth of tourism, if left unchecked, could undermine the very characteristics that make Matheran, an attractive tourist destination. Therefore, it is crucial to recognize the need for environmentally sound development and operations within the tourism sector. Realizing this, necessitates, the implementation of sustainable methods in resort and home stay operations, with special emphasis on managing energy usage. By fostering energy saving operations, it is possible to reduce operational costs while simultaneously enhancing the comfort and quality of services offered to tourists in the resort.
In line with the goal of preserving Matheran’s unique environmental heritage, there is an urgent need to implement measures aimed at reducing the energy footprint of existing resort facilities. This is especially important as no new construction is allowed in Matheran, requiring an emphasis on enhancing the energy performance of current infrastructure. By assessing the present energy consumption patterns in the selected resort and suggesting efficient solutions, the study aims to contribute to a more sustainable and eco-friendly tourism model in Matheran. 8
Thus, the need for this study lies in the identification and implementation of energy conservation strategies that will facilitate the sustainable growth of tourism in Matheran, without compromising the area’s ecological integrity or the quality of services offered to visitors.9
Aim
The main aim is to ensure efficient energy utilization in Matheran resort by conducting a relative assessment of two varied structural shells (envelopes), representing modern and traditional construction, to identify which one offers greater energy savings potential. Further, making the one envelope more energy efficient by applying strategies individually or in combination.
To accomplish this goal, objectives of this study are outlined below:
Exploring energy conservation methods for resorts and their capacity to reduce energy consumption as based on prior findings.
Conducting a relative assessment of distinct building shells (envelopes) in the resort, which are the traditional construction utilizing laterite stone as a load-bearing material and modern reinforced concrete framework with clay brick walls.
Implementing same principle to the resort simulation (computational) model.
Identifying most efficient envelope for energy conservation based on the simulation analysis.
Further, making the modern envelope, energy efficient by using green strategies.
Importance of the Research
The energy efficiency of a building's shell (skin) based on its thermal performance is a way to assess the average heat gain through that envelope.5 It serves as a metric for the energy efficiency of the building, allowing for design flexibility while addressing the retrofitting of the existing resort, which is necessary for Matheran, owing to its status as an eco-sensitive zone since 2003, thereby prohibiting new developments.
For a specific location, climate conditions may remain constant, while architectural elements can differ. Consequently, it is crucial to examine heat gain factors for both envelopes according to their material properties.
![]() | Figure 1: Study framework
|
Source: Author
Energy management in hospitality sector
Resorts significantly use energy and fossil fuels to deliver top-notch services to their guests, which can be efficiently minimized without affecting service quality, leading to potential cost savings.
Energy Consumption for Different Purposes
Resorts are often structured as a fusion of three unique components, with each part serving a distinct function:
![]() | Table 1: Key areas of a resort
|
Source: Author
The energy usage of resorts is affected by both structural and functional attributes
![]() | Figure 2: Factors related to structural and functional attributes that affecting usage of energy in resorts.
|
Source - Author
Energy optimization through passive design solutions
Architectural planning and site orientation, climatic aspects like ambient temperature, relative humidity and radiant heat affect the design.10 As per D. K. Ching, in his book ‘Green building illustrated’, it is imperative to focus on planning, siting, and form of the building while integrating comprehensive solutions for temperature regulation, ventilation, and illumination, thus aiming to reduce power consumption of buildings throughout their operational life.5
![]() | Figure 3: Passive strategies influencing energy usage
|
Source - Author
Buildings are projected to lower energy usage by an average of 20-50% through the implementation of suitable design strategies in various areas, including the building shell (skin), temperature regulation and air conditioning I.e.HVAC, ranging 20-60%, ventilation, illumination ranging 20-50%, hot water supply ranging 20-70%, refrigeration ranging 20-70%, as well as electrical appliances and gadgets like devices and automated systems ranging 10-20%(United Nations Development Program).1
Envelope of the building
The term ‘Shell or Envelope or skin’ signifies the external structure of a building. This shell incorporates structures like walls, glazing, doors, and the roof. Approaching the design of the building from the outside in—starting from the edges of the building site and progressing through its envelope to its interior—offers numerous advantages. By systematically layering and ensuring the integrity and consistency of each layer, significant reductions in various energy loads can be achieved. 5
The main aspects of the shell that determine the performance of the structure are as follows:
![]() | Table 2: Aspects of the building shell
|
Source - Author
The attributes of a building's outer shell, including its shape and direction, the materials used, the quality of construction, and how it interacts with external conditions, influence the thermal influx permeating it, thereby affecting requirement of energy needed for regulating temperature of the space.
Table 3: Sustainable impacts from energy-efficient methods
Approach Method | Benefits | Environmental Benefits | Comment |
Enhancement of building envelopes through the application of ECBC compliance methods for both the building envelope and roof design. | Reduced energy usage Manage the energy consumption of the building during the design phase. Promote building planning and design that is responsive to climate considerations. Predict the future energy demand for air conditioning. Recommend methods for enhancing energy efficiency in structures by utilizing the ECBC compliance. | Lowered greenhouse gas emissions. Offers choices and promotes the use of energy-efficient, building-integrated systems. | It's more advantageous to enhance energy efficiency during the design phase instead of the occupancy phase. |
Source – Author
Properties of outer wall within the structure’s shell
![]() | Image 1
|
Energy modeling software for sustainable building design
Energy simulation involves software-driven evaluative method enabling stackholders to assess structure’s efficiency by implementing required design changes. 11
Softwares used in analysis-
Ecotect - Ecotect is chosen for its visual and spatial thermal analysis capabilities. It allows for early-stage assessment of solar gains, daylighting, and thermal loads, making it ideal for comparing envelope materials and orientation impacts.
Strength: Easy integration with Autodesk tools and climate data files.
Use in this study: To understand surface heat gains, solar exposure, and daylight penetration.
eQUEST - eQUEST is selected for its detailed HVAC energy modeling and annual energy use simulation. It is widely used in industry for simulating cooling/heating loads, enabling performance comparison of retrofitted vs. baseline envelopes.
Strength: Allows precise energy use simulations for buildings.
Use in this study: For assessing cooling load reductions and electricity consumption due to insulation and passive strategies.
Materials and Methods
This study employs a comparative, simulation-based approach to evaluate the energy performance of two building envelope types—traditional (laterite stone) and modern (RCC with clay brick infill)—in a selected resort in Matheran, Maharashtra.
Case Study Selection: A resort featuring both traditional and modern guestroom blocks was chosen to ensure a consistent climatic and functional context for comparison.
Data Collection was done through
On-site surveys to document construction details, orientation, and material use.
Staff interviews to understand appliance usage and energy behavior.
Utility bills and meter readings across seasons to track energy use.
Climatic data from reliable sources for temperature, humidity, and solar exposure.
Envelope Characterization
Traditional envelope: Laterite stone load-bearing walls, Mangalore tile roofing, low insulation.
Modern envelope: RCC frame with clay brick infill, flat slab roof, minimal insulation.
Thermal properties like U-value and thermal mass were derived from field data and standard databases.
Simulation Modelling- Energy simulations were conducted using Ecotect and eQuest, with
Accurate input of Building parameters, dimensions, materials, and internal loads.
Identical usage patterns for comparison.
Focus on annual cooling loads.
Comparative Analysis- Simulation results were analyzed to
Compare energy consumption and thermal comfort.
Identify the more energy-efficient envelope in passive conditions.
Modern Envelope Optimization- The modern envelope was enhanced using
Insulation, shading devices, reflective roofing, natural ventilation, and efficient glazing.
Optimized models were simulated again to assess improvements.
Performance Evaluation- The upgraded modern envelope was benchmarked against
Its original (unmodified) version.
The traditional envelope baseline.
This validated the effectiveness of applied energy-saving strategies.
Overview of the Study Area - Matheran
This hill station lies between the Mumbai-Pune metropolitan corridor, nearly 65 kms from Mumbai in Raigad District, while Pune is situated about 125 km away. The Eco-sensitive area (ESA) of Matheran covers 214.73 sq. km of both the town and its surrounding regions. A significant portion—over 60%—of Matheran is designated as ‘reserved forest’. Its geographical coordinates are 18.9866° North and 73.2679° East.
![]() | Figure 4: Location of Matheran and Matheran map
|
Source – Google Maps and Source – Maps of India
Climatic Data
Owing to its elevated position, it experiences less temperature in winters than the nearby urban centers. Winter extends from November to February, during which the day temperature ranges between 280 C– 310C and the nighttime temperature can drop to about 12°C - 13oC. The annual rainfall is more than 3800 mm mainly from June – September. The summer months are very warm, and the temperature may rise upto 330C – 340C while the nighttime temperature can decrease to mid-twenties.
Locale of Study - resort Woodlands
The Woodlands resort, the structure under investigation, is located within interiors of Matheran thus, it is open from all sides and surrounded by trees. It is interesting to study because of two different types of envelope designs and strategic location. A road that is 4.5 meters wide runs along the north-western edge of the plot. The establishment is a G+1 full-service resort featuring a restaurant, a party hall, a gaming area, and more than 33 guest rooms with configurations of 2, 3, and 4 beds, encompassing a total gross floor area of 1715 m. The primary structure was built in the late 1800s, while the other buildings were erected during the eighties. However, the resort received slight refurbishment approximately 15 years earlier that did not prioritize energy efficiency. Because the surrounding trees shade numerous regions, their proximity has both beneficial and negative consequences. On the one hand, they cause windbreaks by blocking favorable winds and preventing daylight from penetrating.
Orientation and Planning
Oriented diagonally along a NE-SW axis, the structure's long axis; that is, the NW as well as SE facades are larger than the NE and SW facades. The structure chosen for analysis is oriented in direction that TERI recommends.12 It claims that in order to prevent solar heat gain, structures in tropical regions should be oriented with their longer axis running north-south.
While orienting the structure, the site's layout was taken into consideration rather than minimizing heat absorption from the sun on the eastern and western sides. Getting as many open areas in front of as many rooms as possible was the main consideration.
![]() | Figure 5: The Woodlands resort in Matheran
|
Source – Author
Building shell (Envelope) of the resort
Determining how much energy is needed for heating and cooling depends critically on the energy performance of the structure’s shell I.e. facade comprising of walls, slabs, roofing system, fenestration and entry/exits.
Opaque Components
External Walls
The structure is constructed in two ways: the traditional one is an external wall of 350 mm thick Laterite stone, while the modern one is framed by RCC and composed of 230 mm burnt clay brick. The outside and interior walls are painted after they have been covered with cement plaster, which is 18 mm and 12 mm thick, on walls. Light yellow paint has been applied to some of the outside walls to brighten the façade. White or light exterior wall coatings can save 12% on cooling energy, according to Cheung et al. (2005).13
![]() | Figure 6: Wall construction types
|
Source – Author
Roof
The roof of a modern framed structure is roughly 150 mm thick RCC with 50 mm brick bat as a waterproofing course and 20 mm PCC, whereas the traditional Laterite stone structure has a pitched roof with timber frames, steel sheets used for roofing, along with an attic space.
As the roof is exposed to the most solar radiation and is hard to protect with shading, it becomes a key element in a building's energy efficiency.
According to Vijay Kumar et al., concrete roofs in single or two-story buildings in India, typically made with 150 mm thick reinforced cement concrete (RCC) and a waterproof layer of 75–100 mm thick lime brick mortar, contribute to around 50%-70% of the total heat entering the occupant zone. These roofs are primarily responsible for the high electricity costs in air-conditioned buildings.14
Natural ventilation and lighting through a fenestration system
The NE and NW windows are too small and so are ineffective in letting natural light or ventilation. These units must therefore have their lights on for the majority of the day.
According to Handbook on Energy Conscious Buildings by J.K. Nayak and J.A. Prajapati, windows should be positioned diagonally opposite one another for adequate cross ventilation.9 Nevertheless, there are two pairs of windows on the lateral walls of this building, but cross-ventilation is not possible in any of the guest rooms.
Because none of the rooms in the structure are equipped with windows on opposite walls to enable cross-ventilation, answer may be to place two windows adjacent to each other on the same wall instead of a single window. as proposed by the same handbook. Another option, as suggested by the same book, is to feature two windows, one located at the sill and the other situated above the lintel.This proposal would expand the possibilities for fan-induced ventilation and stack ventilation.
Each guest room's ratio of window area to floor space (WFR) as calculated. Similarly, the ratio of window area to wall area(WWR) was calculated. Analysis revealed WWRs ranging from 0.13 to 0.26. Some guest rooms fell below Liping et al.'s (2007) recommended optimum of 0.24.3 While others exceeded this (reaching 0.26), adequate light wasn't achieved due to southeast-facing tree obstructions.
Table 4: Guestrooms' ratio of window area to wall area (WWR) and window area to floor space (WFR)
Rooms | Orientation of Window | Area of room (in Sq.M.) | Area of Window (in Sq.M.) | Area of wall (in Sq.M.) | WFR (Window to floor ratio) | WWR (Window to wall Ratio |
Room 1 & 3 | N-W | 30.5 | 2.88 | 18.7 | 0.094 | 0.15 |
Room 2 | N-W | 30.5 | 4.32 | 18.9 | 0.14 | 0.22 |
Room 4 | N-W | 16 | 2.4 | 13.5 | 0.15 | 0.177 |
Room 5 | N-E | 37.7 | 1.8 | 13.5 | 0.047 | 0.133 |
Room 6 | S-W | 38 | 3.6 | 28.8 | 0.094 | 0.124 |
Room 7 | S-E | 32.5 | 0.6 | 12.3 | 0.018 | 0.048 |
Room 8 | N-E | 44 | 5.4 | 23.7 | 0.122 | 0.227 |
Room 9 & 10 | S-E | 25.6 | 3.6 | 13.5 | 0.14 | 0.266 |
Room 11 & 12 Room 18 & 19 | N-E | 18 | 1.8 | 13.5 | 0.1 | 0.133 |
Room 13 | S-E | 29.5 | 3.6 | 13.5 | 0.12 | 0.266 |
Room 14 | N-W | 16.6 | 3.6 | 15.6 | 0.21 | 0.23 |
Room 15, 16 & 17 | N-W | 15.6 | 2.25 | 10.5 | 0.14 | 0.214 |
Room 20 | N-E | 20.9 | 3.6 | 14.7 | 0.17 | 0.24 |
Room 21 & 23 | N-W | 18 | 1.8 | 13.5 | 0.1 | 0.133 |
Room 22 & 24 | S-E | 18 | 1.8 | 13.5 | 0.1 | 0.133 |
Room 25 & 26 | N-E | 18 | 1.8 | 13.5 | 0.1 | 0.133 |
Room 27 & 29 | N-W | 19.5 | 1.8 | 10.8 | 0.09 | 0.166 |
Room 28 & 30 | S-E | 24.8 | 1.8 | 10.5 | 0.072 | 0.171 |
Room 31, 32&33 | N-W | 15.6 | 2.25 | 10.5 | 0.14 | 0.214 |
Source – Author
Since none of the windows in the remaining guest rooms reach the lintel level (2 meters) from the skirting, their WWRs are below the suggested value of 0.24 (between 0.13 and 0.23).
Summary
The case study resort building's key features are outlined in the table below, along with the references that were used to compare them.
Table 5: An overview of the resort building case study
Characteristics (Building – resort Woodland) | Source | |
Location | Chinoy Road, Matheran, Maharashtra 410102 | |
Orientation | Oriented in 2070 N direction and the front faces North-West | TERI-Best orientation- longer axis north south |
Conditioned floor area | 792 sq.m. | |
No. of floors | G + 1 | |
Building shape | ‘U’ shape with one wing smaller | TERI- EPI of Circular building form is lowest |
Height | 15ft. old building, 10ft. new building (floor to ceiling) | TERI- less is better as it lessens the surface area to floor area ratio i.e. Area ratio |
No.of rooms | 33 rooms | |
Other spaces | Reception area, dining area, party hall, toilets, gaming area, pantry, kitchen, storerooms, staff facility | |
Surroundings | No building shades, tree shades, paver blocks surrounding the building (Reflectance-0.2) | Best is green grass surrounding the building (Reflectance- 0.26) |
Construction | ||
Construction type | Main building- Load bearing | As per ECBC, |
Exterior wall | Laterite stone wall 1 ½ “thick | U factor-0.261W/m2K |
18mm plaster on the exterior | R- value of insulation alone – 3.5 m2K/W | |
12 mm plaster on the interior | ||
Roof | Low pitched roof with gable | |
Corrugated M.S. sheets | ||
No shingles | ||
EPS insulation R-4 | ||
Gypsum false ceiling | ||
Interior Floors | Vitrified tiles | |
Windows | Gross window area: evenly distributed throughout all rooms, accounting for 12% of the conditioned floor area (or 112 square meters). | As per ECBC, vertical fenestration U-factor- 3.3 W/m2K Window wall ratio-0.31-04, so VLT-0.2 |
Single pane window with 6mm frosted glass (U = 5.8 W/m2K, SHGC = 0.82 Wooden frames (U factor-2.8 W/m2K, frame conductance = 0.47, frame width = 60mm) | Maximum SHGC- 0.25 | |
Doors | 1mX2.1m ( U value- U factor-2.8 W/m2K) | |
Exterior shading | No shading and overhangs on windows | |
Construction type | New building-Framed structure with clay brick wall | |
Exterior wall | Clay Brick wall with 230 mm thickness | |
Clay Brick internal walls with 150 mm thickness | ||
18mm exterior plaster | ||
12 mm interior plaster | ||
Roof | R.C.C. flat roof – 150mm | |
Water proofing course -50mm | ||
Interior Floors | Vitrified tiles | |
½” gypsum board ceiling |
Source:Author
Methodology
The methodology used involved creating an Ecotect simulation model of the entire resort, simulating the environment of two guestrooms in eQuest aligned in the same direction, except differing component properties, and implementing energy-efficient measures to one envelope.
![]() | Image 2
|
Creation of a resort model using Ecotect software
![]() | Image 3
|
Designing the building shell for traditional and modern constructions of two guest rooms using eQuest
![]() | Image 4
|
Determining which of the two envelopes provides the highest level of energy efficiency
Development of simulation model
The values assigned to parameters for many aspects of the building, including its the form, placement, and elements of the building envelope were influenced by the materials available.
![]() | Figure 7: Ecotect model of resort
|
The resort was simulated for using Ecotect software, hourly thermal profiles, passive heat gains , and monthly heating and cooling degree days were analyzed.
Passive gains display the heat gains through all the factors, which aids in identifying which parameter to concentrate on in order to reduce the heat.9 The hourly temperature profile shows the interior temperature of each zone to identify the crucial time of day. The cooling need is determined by the monthly degree days.
Hottest day Hourly temperatures profile
Hourly temperature graphs show the temperatures inside and outside of all the model's visible thermal zones during a 24-hour period.
![]() | Figure 8: Resort’s hourly temperature profile
|
Source: Ecotect energy performance simulation tool
According to the bar charts below, the front zone's interior temperature stays lower than that of the back and middle zones.
![]() | Figure 9: Hourly temperature profile comparison bar chart
|
Source: Author
Passive gains Breakdown
![]() | Figure 10: Overall passive gains breakdown graph
|
Source: Ecotect energy performance simulation tool
The passive gains breakdown may be further reduced if thermal barrier is implemented, also the wall and roof parts are white washed, even if Sol-air or indirect heat gain is at its highest.
Evaluation of the two envelopes for energy efficiency
To compare the energy efficiency of the two envelopes, two guestrooms were chosen: one with a 350 mm thick traditional load-bearing Laterite stone construction, and another modern RRC framed with a 230 mm clay brick wall that was same in area, form, orientation, and area of window. The energy-saving potential of the two guest rooms was assessed through simulations conducted in eQuest.
The building properties analysed are listed in the table below:
Table 6: List of building properties analyzed
Properties | Values used for traditional guestroom (Laterite stone wall) | Values used for modern guestroom (brick wall) |
Building configuration | Single -storey, width to depth ratio of 1:2 | Single -storey, width to depth ratio of 1:2 |
Roof and wall properties | ||
Absorptance | Roof- 64 (Red galvanized sheet) Wall-0.4 (Laterite stone) | Roof-0.7 (R.C.C. slab) Wall-0.4 (Red clay bricks) |
Emissivity | Roof-0.88 (Red galvanized sheet) Wall-0.7 (Laterite stone1:2 width to depth ratio, one-story) | Roof-0.54 (R.C.C. slab) Wall-0.7 (Red clay bricks) |
Insulation | Roof-R-value-4.68 m2.K/W Air film outside-R-0.06 Al sheets-R-value-0.14 Wooden floor – R-0.6 Expanded polystyrene-R- 3.75 Air layer inside-R- 0.13 Wall-R-value-1.52 m2.K/W (Laterite stone) Air film outside-R-0.06 18mm outside plaster-R-0.025 380mm laterite stone wall-R-1.28 12mm inside plaster-R-0.02 Air layer inside-R-0.14 | Roof-0.424 (R.C.C. slab) Air film outside-R-0.06 20 mm PCC-R- 0.03 50mm Brick bat – R – 0.08 150mm RCC slab-R-0.104 12mm inside plaster-R-0.02 Inside ceiling air layer-R-0.13 Wall-R-0.685 m2.K/W (Red clay bricks) Air film outside-R-0.06 18mm outside plaster-R-0.025 230mm clay brick wall-R-0.44 10mm inside plaster-R-0.02 Air layer inside-R-0.14 |
Construction Type | Load bearing construction with 380mm thick laterite stone wall and wooden frames with Al commercial sheets with 20mm expanded polystyrene under the board insulation | R.C.C. framed structure with 230mm clay brick wall and 150mm thick slab with brick bat and PCC |
Fenestration (Openings) | ||
Distribution of Windows | Windows (12% of floor area), only on the front side (North-west) | Windows (12% of floor area), distributed in two orientations (North-east & South-east) |
Exterior shading | Verandah projection acts as shading | No overhangs |
Glazing U-factor | 1.09 (6mm frosted glass) | 1.09 (6mm frosted glass) |
Glazing SHGC | 0.72(6mm frosted glass) | 0.72(6mm frosted glass) |
Source: Author
Different values were assigned to the respective parameters in order to analyze the effect of changing attributes of various construction assemblies and elements. The three building assemblies and elements are (i) layout, (ii) the walls as well as roof, and (iii) the windows. The impact of thermal mass on specific measures was also examined by plotting the hourly temperature variation, heat gains and losses per hour, monthly energy demands and discomfort levels and fabric-derived heat gains.5
Roof and Wall Properties
Heat gain or loss via the building envelope is determined by the exposed surfaces' emissivity, absorptance, and R-value. Because of the difference in the angle of incident solar radiation, the roof and walls contribute to varying amounts of thermal influx. Therefore, the impact of R-value, absorptance, and emissivity was analyzed for both the roof and the walls.13
Table 7: Properties of the walls and roof assumed for simulation.
Properties of roof/wall | Old Traditional building | New modern building | As per ECBC | |||
Wall | Roof | Wall | Roof | Wall | Roof | |
Solar reflectivity | 0.6 | 0.36 | 0.6 | 0.3 | >0.7 | >0.7 |
Surface emissivity | 0.7 | 0.88 | 0.7 | 0.54 | >0.75 | >0.75 |
Absorptance | 0.4 | 0.64 | 0.4 | 0.7 | 0 | 0 |
Insulation (Resistance R-value) | 1.525 m2.K/W | 4.68 m2.K/W | 0.685 m2.K/W | 0.42 m2.K/W | 2.1 m2.K/W | 3.5 m2.K/W |
Source: Author
Fenestration (Openings) Properties
The U-factor, SHGC, shading and window distribution in various orientations all affect how much heat is gained or lost via windows. Two-layer, low-emissivity, triple-glazed windows are associated with lower U-factor values, while the building’s existing single-pane glazing, is related with greater values. In a similar way, high SHGC values are linked to clear glazing, while lower values are linked to tinted or reflective glazing. The fenestration characteristics of modern and traditional envelopes are similar. 5
Table 8: Window characteristics for modeling
Fenestration Properties | Old Traditional building | New modern building | As per ECBC, WWR?40% |
U-value | 1.09 W/m2.K | 1.09 W/m2.K | 3. 3W/m2.K |
SHGC | 0.72 | 0.72 | 0.25 |
Comparative of Two Envelopes
Study is done on both guest rooms to determine the most energy-efficient envelope derived from the assessment of energy-saving opportunities in various elements like the walls, roof, and window features.
![]() | Table 9: Chart Comparing the Two Envelopes
|
Source:Author
Result
This investigation aims to assess and compare the energy efficiency of two distinct guestroom: a traditional guestroom with a Laterite stone structure and a modern guestroom with an RCC (Reinforced Cement Concrete) structure. The analysis's main goal is to evaluate each design's thermal performance and energy efficiency. Simulations were carried out using Ecotect and eQuest to analyze the thermal behavior of both building types under typical climatic conditions. The results highlight the influence of different materials, insulation strategies, and building configurations on overall energy consumption for cooling.8
As discussed, simulations were performed on the existing traditional and modern guestrooms. The results are analysed in the following sections. The thermal analysis was done in Ecotect and eQuest. In general, the traditional guestroom which is made up of 350mm thick Laterite stone has R-value of 1.52m2k/W and has higher thermal mass as compared to the 230mm thick clay brick wall. Also, though the roof is corrugated aluminum sheet, but the traditional guest room has an attic as well as roof insulation of 1” EPS. Thus, it resulted in significant savings.
The modern guestroom is an RCC building with an uninsulated clay brick wall that is 230 mm thick.The roof is also RCC without insulation, thus even though with same building configuration, orientation, shape, size, the energy saving is less. The graph below, which corresponds to the May month, which is hottest, showed the modern guestroom's cooling energy consumption 1.21 times greater than that of the traditional guestroom during highest temperatures.
![]() | Figure 11: Monthly space cooling energy consumption by end-use
|
The energy needed to cool the similar space in a modern guest room is 1288kW, whereas energy needed for space cooling in a traditional guestroom is 1109kW for a year. Therefore, 15% more energy is needed for the modern envelope than for the traditional one.
Thermal Analysis In Ecotect
This facilitates the comparison of the two envelopes by assessing the hourly temperature variation, hourly heat gains and losses, and the breakdown of passive heat gains.
Hourly Temperature Profile For Average Hottest Day
![]() | Figure 12: Traditional envelope’s Hourly temperature profile
|
Source: Ecotect energy performance simulation tool
![]() | Figure 13: Hourly temperature profile of modern envelope Source: Ecotect energy performance simulation tool
|
The hourly thermal profiles of the modern and traditional envelopes reveal that, from 6 a.m. to 9 p.m., traditional guestroom’s typically colder than its modern counterpart. Consequently, compared to modern guestrooms, the traditional guestroom remains approximately 5% cooler.
In contrast to the modern structure shell with 230mm thick clay brick wall of R-value- 0.685 m2k/W, traditional structure shell with 350mm thick Laterite stone wall has a higher thermal mass, which accounts for the temperature differential. In addition, the roof assembly's R-value is 4.68 m2k/W higher than the modern one's, which is 0.424 m2k/W. In contrast to the modern envelope's roof finished with PCC, traditional envelope's aluminium sheet roof has a higher reflectivity. Additionally, a traditional roof has a higher emissivity than a modern one. All of this aids in keeping the old envelope's temperature higher than the modern one.
Table 10: Comparison of the two guestrooms' hourly temperature profiles
Traditional guestroom | Modern guestroom |
Hourly temperature profile | |
HOURLY TEMPERATURES - One day in May (C) (C) (C) ----- ------- -------- --------- 00 26.0 28.5 -2.5 01 26.0 28.0 -2.0 02 26.0 27.5 -1.5 03 26.0 27.3 -1.3 04 26.0 27.6 -1.6 05 26.0 28.1 -2.1 06 26.0 29.0 -3.0 07 26.0 30.4 -4.4 08 33.9 31.9 2.0 09 35.0 33.5 1.5 10 35.3 34.8 0.5 11 36.1 35.8 0.3 12 36.2 36.3 2.2 13 36.5 36.4 0.1 14 36.6 36.0 2.1 15 36.4 35.2 2.2 16 36.0 34.0 2.0 17 34.7 32.7 2.0 18 33.8 31.5 2.3 19 33.4 30.4 3.0 20 33.2 29.6 3.6 21 33.0 29.1 3.9 22 26.0 28.9 -2.9 23 26.0 28.8 -2.8 | HOURLY TEMPERATURES - One day in May (C) (C) (C) ----- ------- -------- --------- 00 26.0 28.5 -2.5 01 26.0 28.0 -2.0 02 26.0 27.5 -1.5 03 26.0 27.3 -1.3 04 26.0 27.6 -1.6 05 26.0 28.1 -2.1 06 35.0 29.0 6.0 07 35.1 30.4 4.7 08 35.4 31.9 3.5 09 35.8 33.5 2.3 10 36.4 34.8 1.6 11 36.7 35.8 0.9 12 36.7 36.3 0.4 13 37.1 36.4 0.7 14 36.8 36.0 0.8 15 36.8 35.2 1.6 16 36.7 34.0 2.7 17 36.4 32.7 3.7 18 36.2 31.5 4.7 19 36.1 30.4 5.7 20 36.1 29.6 6.5 21 35.9 29.1 6.8 22 26.0 28.9 -2.9 23 26.0 28.8 -2.8 |
Source: :Ecotect energy performance simulation tool
![]() | Figure 14: Comparison of the two guestrooms' hourly temperature profiles Source: :Ecotect energy performance simulation tool
|
Hourly heat transfer data indicates that the fabric gain in the modern envelope is often more significant than in the traditional one. This increase occurs greater from 7 a.m. to 6 p.m. The substantial thermal mass of the walls combined with the EPS insulation in the ceiling cause the traditional guestroom to gradually increase in temperature.
But in modern guestrooms the slope of fabric gains is steep after 7am due to lack of insulation on wall as well as roof.
Table 11: Breakdown of passive heat gains for both envelope types. Source: Ecotect energy performance simulation tool.
Traditional Guestroom | Modern Guestroom |
Passive gains breakdown | |
FROM: 1st January to 31st December CATEGORY LOSSES GAINS ------------ ------- ------ FABRIC 4.4% 6.1% SOL-AIR 0.0% 8.4% SOLAR 0.0% 6.7% VENTILATION 5.0% 7.5% INTERNAL 0.0% 70.1% INTER-ZONAL 90.6% 1.3% | FROM: 1st January to 31st December CATEGORY LOSSES GAINS ------------ ------- ------ FABRIC 2.2% 13.8% SOL-AIR 0.0% 20.1% SOLAR 0.0% 2.5% VENTILATION 0.8% 6.2% INTERNAL 0.0% 51.5% INTER-ZONAL 96.9% 5.9% |
Discussion
The analysis of the simulations points to the traditional guestroom being more energy efficient than the modern one. Compared to modern construction, the traditional construction in Laterite stone resulted in 17% energy savings due to its wall’s thermal mass and insulation in the roof.
“The lower cooling demand in the traditional guestroom is attributed to the high thermal mass of Laterite stone and effective roof insulation. These findings align with Givoni (1998), who emphasized the role of thermal mass in passive cooling. The lack of insulation in the modern envelope significantly increases heat gains, indicating a need for retrofit strategies.10 Additional research results in a more energy-efficient envelope for the modern guestroom by altering its fenestration, wall, and roof R-values as well as its emissivity and absorptance properties.
Retrofitting Modern guestroom
In one-storey building, the heat absorption and dissipation from the walls and roof account for larger percentage of the building energy use. As a result, upgrading the walls and roof may also save energy.
Therefore, the most effective way to enhance the energy efficiency of the modern guestroom is by adding insulation, with placing it above the deck being more effective than below, as it prevents heat from entering the structure.
Application of Green Roof
The following factors are taken into account when choosing a green roof for the current modern guestroom retrofit:
Energy consumption in buildings.
biodiversity and habitat.
roof life.
air quality; and
the decrease of storm water flow
Aesthetics and recreation
The table below mentions the green roof's thermal characteristics:
Table 12: Thermal parameters of green roof
Insulation | Thickness (m) | Thermal conductivity(k) | R-value (m2.k/W) |
Layer of Gravel drainage | 0.06 | 0. 27 | 0.24 |
Total assembly | 0.1 | 2.15 | |
Polyisocyanurate Insulation | 0.05 | 0.02 | 2.13 |
RCC roof | 0.175 | 1 | 0.42 |
Total | 0.425 | 1.29 | 5.6 |
Insulating surfaces with high absorptance and low emissivity is a more efficient way to save energy. Therefore, green roof insulation seems to be the optimal choice.2
Wall Insulation
Since EIFS (External Insulation and Finish System) is over the deck insulation and reduces heat entry into the building structure itself, it was employed for simulation purposes for wall insulation. The following factors were taken into account before choosing EIFS. 7
Insulation used over the deck
Water resistant.
Sustainable (Eco-certified)
Offers better energy efficiency than insulation placed beneath the board.
The specifications of EIFS is as follows
Table 13: Thermal parameters of EIFS
Material | R value |
230 mm clay brick wall | 0.68 |
EIFS | 4 |
Total | 4.68 |
![]() | Figure 15: Hourly thermal profile comparative between modern and insulated modern envelopes
|
Aforementioned chart shows how the hourly temperature profile in the insulated modern envelope differs from the regular, due to the application of insulation on the roof and wall. The hourly temperature profile of the shell (envelope) is 12% lower than its counterpart as a result of this insulation. Additionally, although the daily temperature on average outside is 31.3°C, or 8% lower than the outside temperature, the average temperature inside drops from 32.8°C to 28°C.
Thus, it is seen in thermal analysis that the insulated modern envelope responses much better than the modern envelope and is a better option to be utilized in Matheran which will help reduce the cooling costs and because of green roof, it will help in maintaining the ecology of the area.
The traditional guestroom performed better in terms of energy efficiency, requiring 15% less energy for cooling than the modern guestroom. This was due to the traditional guestroom's higher thermal mass (350mm Laterite stone) and roof insulation. The modern guestroom, with 230mm brick walls and no insulation, had higher cooling energy usage.
Thermal analysis showed that the traditional guestroom maintained cooler temperatures throughout the day, especially due to its higher R-value walls and better roof insulation. The modern guestroom gained more heat due to lack of insulation.
Retrofitting the modern guestroom with EIFS wall insulation and a green roof significantly improved its energy performance, reducing cooling needs and internal temperatures, making it more energy-efficient and environmentally friendly.
Conclusion
The comparative evaluation aimed to determine the more effective building envelope between traditional and modern guestrooms while optimizing the energy efficiency of the contemporary design for Matheran's warm and humid climate. The results indicated that the traditional load-bearing guestroom constructed with Laterite stone outperformed the RCC and clay brick modern structure in terms of reducing peak cooling demands. This traditional model achieved approximately 17% energy savings due to the thermal inertia of its walls combined with roof insulation. Key elements for minimizing energy consumption associated with cooling include enhanced R-values, greater surface reflectivity, and high emissivity in roofing materials. The traditional envelope, in comparison, demonstrated a 65% reduction in fabric heat gains.
Given that current construction practices typically employ RCC and brick systems, the study extended its focus to improving the modern guestroom. Since Matheran is protected under eco-sensitive regulations that prohibit new construction, the approach involved enhancing the existing structure through over-deck insulation rather than under-deck alternatives or rebuilding entirely. The use of green roofing in combination with an EIFS (External Insulation and Finish System) comprising polyisocyanurate insulation for the roof and EPS panels for the walls led to a 10% improvement in the hourly indoor temperature profile compared to the uninsulated version. When insulation was applied to both the walls and roof of the modern guestroom, a 22% decline in fabric heat gains was observed, significantly aiding in the reduction of cooling energy requirements. Consequently, the cooling load for the insulated contemporary room dropped by 20%, which translated into a 24% decrease in yearly electricity consumption. Altogether, the implementation of these energy-efficient strategies has the potential to yield energy savings of up to 55%
Technical Recommendations for Industry and R and D
Roof insulation enhancement can be done with the use of polyisocyanurate insulation boards (higher R-value) for better thermal resistance and increase roof reflectance using cool roofing materials (white or high-albedo coatings). Future research should explore alternative eco-friendly insulation materials that provide high thermal resistance while being locally sourced and sustainable.
Wall insulation and envelope design can be enhance by applying EIFS with EPS or mineral wool to minimize heat gain and consider ventilated facades to improve heat dissipation.
Passive cooling strategies can be integrated through green roofs and shading elements to lower indoor temperatures and utilize high-performance glazing for better thermal control. Further research can be on development of climate-responsive building envelopes that incorporate passive cooling techniques like ventilated facades, and shading devices can further enhance energy efficiency.
Energy monitoring and smart systems can be implemented through real-time IoT-based energy monitoring for efficient cooling load management.
Encouraging government incentives for adopting energy-efficient retrofitting solutions in eco-sensitive zones like Matheran can accelerate the transition towards sustainable hospitality architecture
Acknowledgement
The author would like to thank YCMOU for granting M.Arch degree for my research work. The Department of Architecture at Bharati Vidyapeeth College of Architecture, Navi Mumbai of the Mumbai University, is highly appreciated for guiding me throughout my research. The author is also profoundly grateful to the professors at Bharati Vidyapeeth College of Architecture, Navi Mumbai for their guidance during the research.
Funding Sources
The author received no financial support for the research, authorship, and/or publication of this article.
Conflict of Interest
The author does not have any conflict of interest.
Data Availability Statement
The manuscript incorporates all datasets produced or examined throughout this research study.
Ethics Statement
This research did not involve human participants, animal subjects, or any material that requires ethical approval.
Informed Consent Statement
This study did not involve human participants, and therefore, informed consent was not required.
Author Contributions
The sole author was responsible for the conceptualization, methodology, data collection, analysis, writing, and final approval of the manuscript.
References
- Callithen N, Matthew N. United Nations Development Program (UNDP). Cleveland Council of World Affairs; 2007.
- Milojkovi? A, Nikoli? M, Stankovi? V. Improvement of energy efficiency in hospitality - towards sustainable resort. PhIDAC. 2012
- Liping W, Nyuk Hien W. The impacts of ventilation strategies and facade on indoor thermal environment for naturally ventilated residential buildings in Singapore. Build Environ. 2007;42(12):4006-4015.
CrossRef - U.S. Department of Energy. Annual Report. 2004
- Ching FDK, Shapiro IM. Green Building Illustrated. 2nd ed. Wiley; 2020.
- Krishnan A, Baker N, Yannas S, Szokolay S. Climate Responsive Architecture – A Design Handbook for Energy Efficient Buildings. McGraw Hill Education; 2001.
- Bureau of Energy Efficiency (BEE), British High Commission, ICF International. Energy Management in Your resort. New Delhi 2008.
- Bureau of Energy Efficiency (BEE), USAID ECO-III Project. Energy Conservation Building Code (ECBC) User Guide. July 2009.
- Nayak JK, Prajapati JA. Handbook on Energy Conscious Buildings. Indian Institute of Technology Bombay; May 2006.
- Givoni B. Climate Considerations in Building and Urban Design. Van Nostrand Reinhold; 1998.
- Wulfinghoff DR, Rawal R, Garg V, Mathu J. Energy Conservation Building Code Tip Sheet, Energy Simulation, Version 2.0. USAID ECO-III Project, International Resources Group; July 2010.
- The Energy and Resources Institute (TERI). Development of Building Regulations and Guidelines to Achieve Energy Efficiency in Bangalore City. 2009.
- Cheung CK, Fuller RJ. Energy-efficient envelope design for high-rise apartments. Energy Build. 2005;37:37-48.
CrossRef - Vijaykumara KCK, Srinivasan PSS, Dhandapani S. A performance of hollow clay tile (HCT) laid reinforced cement concrete (RCC) roof for tropical summer climates. Energy Build. 2007;39:886-892.
CrossRef